Environmentally Protected Control Panel
- 80-character LCD alphanumeric programming/diagnostics display
- Preset output current and voltage capability
- Sealed tactile keypad
- DC ON indicator
- Fault indicator and alarm
Digital Meters
Large (0.5"), bright LED digital displays for easy viewing of output voltage (four digits) and current (six digits).
Totalizing Ampere-Time Meter
Available as either a resettable or non-resettable totalizer, accumulated ampere-time is shown on the alphanumeric display. The operator can easily select the unit of measure in ampere-hours, ampere-minutes or ampere-seconds.
Variable Ramp
The operator can select an output ramp time between 0-100 minutes, in one-second increments. When the power supply is started, the output will rise to the desired voltage or current over the ramp time selected.
Cycle Timer
A cycle timer will sound an alarm and/or shut off the power supply (user selectable) when the operator-selected cycle time has been reached. A cycle time up to 1000 hours can be selected, in one-second increments. Contacts are available for an external alarm.
Fault Diagnostics
In the unlikely event a fault occurs, the LCD automatically displays the following potential fault conditions:
- Transformer overtemperature
- Thyristor overtemperature
- Two application-specific faults
Enclosures
Enclosures up to 72" H are available in either powder-coated steel or PVC at no additional cost. Optional Type 316L stainless steel enclosures are available.
(Contact factory for pricing)
Automatic Voltage Stabilization (AVS)
Maintains the output voltage constant to within ±0.5% of rated voltage from 0-100% of the rated voltage.
Automatic Constant Current (ACC)
Maintains the output current constant to within ±0.5% of rated current from 0-100% of the rated current.
Automatic Crossover
When operating in the voltage stabilization mode, transfer will occur to the constant current mode when the output current reaches the preset current limit. Conversely, when operating in the constant current mode, transfer will occur to the voltage stabilization mode when the output voltage reaches the preset limit.
Protection Features
- Fast-acting thyristor fuses
(on units up to 2,500 amperes)
- Electronic thyristor protection
(on units 2,500 amperes and above)
- Transformer overtemperature shutdown
- Thyristor overtemperature shutdown
- Fan overload shutdown
- Control transformer fuses
Remote Control
The remote control console features an environmentally protected keypad, digital ampere and voltage meters, 80-character display for operation setup and fault information, ampere and voltage adjust pushbuttons, DC ON and fault indicator LED's.
(Standard on three phase, optional on single phase)
Digital Interface
Any number of rectifiers can be connected via two wires to a PLC or computer. The Rapid digital communications interface will support industry standard and proprietary protocols, allowing simple installation and eliminating the need for analog output modules on the PLC or computer.
Analog Interface
For new or existing installations where an analog interface is required, the controls can be provided with an isolated 4-20 ma, 01, 5 or 10 V computer interface option.
Programmable Ampere-Time Meter with Preset
The ampere-time with preset feature can be programmed to alarm and/or shut off the power supply after the preset ampere-time is reached. This option also includes the standard ampere-time totalizer.
Average Current Density (ACD)
The DC output is varied in direct proportion to the load, maintaining an average current density over varying loads.
Reduced Ripple
For applications requiring lower ripple, Rapid offers power supplies with output ripple as low as 1% of the operating setpoint.
General Specifications
-
| Input Voltage: | Up to 600 VAC, single and three-phase, 50 or 60 Hz
(other voltages or frequencies available upon request) |
| Output Current: | Up to 50,000 ADC (higher current ratings available upon request) |
| Output Voltage: | Up to 600 VDC (higher voltage ratings available upon request) |
| Ripple: | 5% rms ripple @ full rated output (three phase units) |
| Cooling: | Convection, forced air, direct water, closed loop water, self- contained water |
| Magnetics: | Low loss grain-oriented silicon steel cores, all copper conductors,
220° C rated insulation, design temperature rise < 80° C |
| Operation: | Continuous at full rated voltage and current at up to 40° C ambient
temperature |